SMA SUNNY ISLAND 3.0M Operating Manual page 63

Sunny remote control
Hide thumbs Also See for SUNNY ISLAND 3.0M:
Table of Contents

Advertisement

SMA Solar Technology AG
No.
Name
W 339 ExtVtgIncPro
W 340 ExtVtgIncProSlv1
W 341 ExtVtgIncProSlv2
W 343 AcVtglim
W 344 AcVtglimSlv1
W 345 AcVtglimSlv2
Operating Manual
Level Cause
1
Voltage increase protection Line
conductor L1
1
Voltage increase protection of
line conductor L2
1
Voltage increase protection Line
conductor L3
1
Disconnection from the ex-
ternal grid due to insufficient
battery voltage or overvolt-
age at line conductor L1: The
master disconnects from the ex-
ternal energy source because
the voltage at connection AC2
is too high or the battery volt-
age too low.
1
Disconnection from the ex-
ternal grid due to insufficient
battery voltage or overvolt-
age at line conductor L2:
Slave 1 disconnects from the ex-
ternal energy source because
the voltage at connection AC2
is too high or the battery volt-
age too low.
1
Disconnection from the ex-
ternal grid due to insufficient
battery voltage or overvolt-
age at line conductor L3:
Slave 2 disconnects from the ex-
ternal energy source because
the voltage at connection AC2
is too high or the battery volt-
age too low.
10 Troubleshooting
Corrective measures
• Ensure that the conductor cross-
section of the AC cables is correctly
sized.
• Contact the Service, if required (see
Section 16 "Contact", page 161).
SI30M-44M-60H-80H-BE-en-33
63