13 Parameters in Sunny Remote Control
No.
Name
232.14
GdFrqMinDel Lower frequency differ-
232.15
GdFrqMaxDel Upper frequency differ-
232.16
GdAlSns
232.40
GdRtCurSrc
232.41
P-WCtlHzMod Operating mode of ac-
232.42
P-HzStr
132
SI30M-44M-60H-80H-BE-en-33
Description
ence for valid grid con-
nection in Hz (expert
mode, protected by
SMA Grid Guard)
ence for valid grid con-
nection in Hz (expert
mode, protected by
SMA Grid Guard)
Sensitivity of the anti-is-
landing detection (ex-
pert mode, protected
by SMA Grid Guard)
Place of reactive current
compensation in grid
operation (expert
mode)
tive power reduction in
case of overfrequency
P(f) (expert mode, pro-
tected by
SMA Grid Guard)
Difference between
starting frequency and
grid frequency, linear
instantaneous power
gradient configuration
(protected by
SMA Grid Guard)
Value
Explanation
0.00 Hz to
2.50 Hz
0.00 Hz to
VDE_AR_4105
2.50 Hz
0.00 Hz
230 V / 50 Hz
0.20 Hz
0.00 Hz
220 V / 60 Hz
0.20 Hz
Low
Low
Medium
Medium
Standard
Standard
High
High
External
Sunny Island com-
pensates all reactive
currents.
Inverter
Sunny Island does
not compensate reac-
tive currents.
Shared
Sunny Island partially
compensates reactive
currents.
Off
Disable
WCtlHz
Enable
0.0 Hz to 5.0 Hz
This value defines
how many Hz above
210.02 InvFrqNom
the active power limi-
tation starts.
SMA Solar Technology AG
Default
Value
✓ ✓ 0.02 Hz
✓ ✓ 1.45 Hz
0.02 Hz
0.02 Hz
✓ ✓ Standard
✓ ✖ External
✓ ✓
✓ ✖ 0.2 Hz