SMA SUNNY ISLAND 3.0M Operating Manual page 60

Sunny remote control
Hide thumbs Also See for SUNNY ISLAND 3.0M:
Table of Contents

Advertisement

10 Troubleshooting
No.
Name
W 315 ExtVtgLo
W 316 ExtVtgLoSlv1
W 317 ExtVtgLoSlv2
W 319 ExtVtgHi
W 320 ExtVtgHiSlv1
W 321 ExtVtgHiSlv2
60
SI30M-44M-60H-80H-BE-en-33
Level Cause
1
Disconnection from the ex-
ternal grid due to undervolt-
age at line conductor L1: The
voltage of the generator or the
utility grid at the master is too
low.
1
Disconnection from the ex-
ternal grid due to undervolt-
age at line conductor L2: The
voltage of the generator or the
utility grid at slave 1 is too low.
1
Disconnection from the ex-
ternal grid due to undervolt-
age at line conductor L3: The
voltage of the generator or the
utility grid at slave 2 is too low.
1
Disconnection from the ex-
ternal grid due to overvolt-
age at line conductor L1: The
voltage of the generator or the
utility grid at the master is too
high.
1
Disconnection from the ex-
ternal grid due to overvolt-
age at line conductor L2: The
voltage of the generator or the
utility grid at slave 1 is too high.
1
Disconnection from the ex-
ternal grid due to overvolt-
age at line conductor L3: The
voltage of the generator or the
utility grid at slave 2 is too high.
SMA Solar Technology AG
Corrective measures
Corrective measures for a genera-
tor:
• Adjust the thresholds for generator
voltage on the Sunny Island (see
the Sunny Island inverter installation
manual). Observe and analyze the
measured values 134.02 ExtVtg
during operation.
• Adjust the generator voltage and/
or generator frequency.
Corrective measures in battery
backup systems:
• Contact the Service, if required (see
Section 16 "Contact", page 161).
Corrective measures for a genera-
tor:
• Adjust the thresholds for generator
voltage on the Sunny Island (see
the Sunny Island inverter installation
manual). Observe and analyze the
measured values 134.02 ExtVtg
during operation.
• Adjust the generator voltage and/
or generator frequency.
Corrective measures in battery
backup systems:
• Contact the Service, if required (see
Section 16 "Contact", page 161).
Operating Manual