13 Parameters in Sunny Remote Control
No.
Name
232.52
PF-PFExtStr
232.53
PF-WNomStr
232.54
PF-PFStop
232.55
PF-PFExtStop
232.56
PF-WNomS-
top
232.58
GdAIFac
232.59
MsPhSel
134
SI30M-44M-60H-80H-BE-en-33
Description
Excitation type of the
start point, configura-
tion of cos Phi(P) char-
acteristic curve, direct
specification (expert
mode, protected by
SMA Grid Guard)
Active power of the
start point, configura-
tion of cos Phi(P) char-
acteristic curve, direct
specification (expert
mode, protected by
SMA Grid Guard)
CosPhi of the end point,
configuration of
cos Phi(P) characteristic
curve, direct specifica-
tion (expert mode, pro-
tected by
SMA Grid Guard)
Excitation type of the
end point, configuration
of cos Phi(P) character-
istic, direct specification
(expert mode, pro-
tected by
SMA Grid Guard)
Active power of the end
point, configuration of
cos Phi(P) characteristic
curve, direct specifica-
tion (expert mode, pro-
tected by
SMA Grid Guard)
Anti-islanding factor in
current-controlled grid
operation with I-Loop
(expert mode)
Line conductor to which
the Sunny Island is con-
nected (expert mode,
protected by
SMA Grid Guard)
Value
Explanation
OvExt
Lagging
UnExt
Leading
0% to 232.56 PF-
WNomStop
0.8 to 1.0
OvExt
Lagging
UnExt
Leading
232.52 PF-
WNomStr
to 100%
0.00 to 3.00
L1
Line conductor L1
L2
Line conductor L2
L3
Line conductor L3
SMA Solar Technology AG
Default
Value
✓ ✓ OvExt
✓ ✓ 50 %
✓ ✓ 0.9
✓ ✓ UnExt
✓ ✓ 100 %
✓ ✓ 0.50
✓ ✖