SMA SUNNY ISLAND 3.0M Operating Manual page 137

Sunny remote control
Hide thumbs Also See for SUNNY ISLAND 3.0M:
Table of Contents

Advertisement

SMA Solar Technology AG
No.
Name
234.03
GnCurNom
234.04
GnFrqNom
234.05
GnFrqMin
234.06
GnFrqMax
234.07
GnStrMod
234.08
GnOpTmMin Minimum run time of gen-
234.09
GnStpTmMin Minimum stop time of the
234.10
GnCoolTm
Operating Manual
Description
Nominal generator cur-
rent in A
Nominal generator fre-
quency under nominal
load in Hz (expert mode)
Lower minimum threshold
of generator frequency
for frequency monitoring
in Hz (expert mode)
Upper maximum thresh-
old of generator fre-
quency for frequency
monitoring in Hz (expert
mode, protected by
SMA Grid Guard)
Generator interface
erator in minutes
generator in minutes
Cooling time of the gen-
erator in minutes
13 Parameters in Sunny Remote Control
Value
Explanation
0.0 A to 50.0 A
1 Sunny Island
0.0 A to 100.0 A
Two Sunny Island
inverters, parallel
0.0 A to 150.0 A
Three Sunny Is-
land inverters,
parallel
0.0 A to 50.0 A
Three-phase
0.0 A to 80.0 A
Multicluster-Box 6
0.0 A to 160.0 A
Multicluster-Box
12 (MC-
BOX-12.3)
0.0 A to 200.0 A
Multicluster-Box
12 (MC-
BOX-12.3-20)
0.0 A to 500.0 A
Multicluster-Box
36
234.05 GnFrqMin t
230 V / 50 Hz
o
220 V / 60 Hz
234.06 GnFrqMax
40.00 Hz to
230 V / 50 Hz
234.04 GnFrqNom
50.00 Hz to
220 V / 60 Hz
234.04 GnFrqNom
234.04 GnFrqNom
230 V / 50 Hz
 to 70.00 Hz
220 V / 60 Hz
Manual
Manual
Autostart
Automatic
0 min to 360 min
0 min to 360 min
0 min to 60 min
SI30M-44M-60H-80H-BE-en-33
Default
Value
✖ ✓ 16.0 A
16.0 A
16.0 A
16.0 A
60.0 A
160.0 A
200.0 A
435.0 A
✖ ✓ 50.00 Hz
60.00 Hz
✖ ✓ 44.64 Hz
50.00 Hz
✖ ✓ 60.00 Hz
70.00 Hz
✖ ✓ Autostart
✖ ✓ 15 min
✖ ✓ 15 min
✖ ✓ 5 min
137