SMA Solar Technology AG
No.
Name
222.09
ChrgVtgEqu
222.10
ChrgVtgFlo
222.11
BatTmpCps
222.12
AutoEquChrgEna
222.13
BatChrgVtgMan
223# Protection
No.
Name
223.01
BatPro1TmStr
223.02
BatPro1TmStp End time of battery protection mode level
223.03
BatPro2TmStr
223.04
BatPro2TmStp End time of battery protection mode level
223.05
BatPro1Soc
223.06
BatPro2Soc
Operating Manual
Description
Cell voltage setpoint for
equalization charge in V
(expert mode)
Cell voltage setpoint for
float charge in V (expert
mode)
Battery temperature com-
mV
pensation in
/
(ex-
°C
pert mode)
Automatic equalization
charge (expert mode)
Manual setpoint of the
battery charging voltage
with disabled battery
management in V (expert
mode)
Description
Start time of battery protection mode level
1 in hh:mm:ss (expert mode)
1 in hh:mm:ss (expert mode)
Start time of battery protection mode lev-
el 2 in hh:mm:ss (expert mode)
2 in hh:mm:ss (expert mode)
Battery SOC for protection mode level 1
as % (expert mode)
Battery SOC for protection mode level 2
as % (expert mode)
13 Parameters in Sunny Remote Control
Value
Explanation
2.30 V to 2.70 V
Off-grid
VRLA, on-grid
FLA, on-grid
2.20 V to 2.40 V
–
mV
0.0
⁄
to
–
°C
mV
10.0
⁄
°C
Disable
Disable
Enable
Enable
41.0 V to 63.0 V
–
Value
00:00:00 to
23:59:59
00:00:00 to
23:59:59
00:00:00 to
23:59:59
00:00:00 to
23:59:59
0% to 70%
0% to 70%
SI30M-44M-60H-80H-BE-en-33
Default
Value
✖ ✓ 2.45 V
✓ ✖ 2.55 V
✓ ✖ 2.50 V
✓ ✓ 2.25 V
mV
✓ ✓ 4.0
⁄
°C
✓ ✓ Enable
✓ ✓ 54.0 V
Default
Value
✖ ✓ 22:00:00
✖ ✓ 06:00:00
✖ ✓ 17:00:00
✖ ✓ 09:00:00
✖ ✓ 20 %
✖ ✓ 15 %
127