SMA SUNNY ISLAND 3.0M Operating Manual page 136

Sunny remote control
Hide thumbs Also See for SUNNY ISLAND 3.0M:
Table of Contents

Advertisement

13 Parameters in Sunny Remote Control
No.
Name
233.06
GdTm1Str
233.07
GdTm2Str
233.08
GdPwrEna
233.09
GdPwrStr
233.10
GdPwrStp
233.11
GdStrChrgMo
d
234# Gen Control
No.
Name
234.01
GnVtgMin
234.02
GnVtgMax
136
SI30M-44M-60H-80H-BE-en-33
Description
Start of standard addi-
tional time period for grid
request in hh:mm:ss (ex-
pert mode)
Start of additional time pe-
riod for grid request in h-
h:mm:ss (expert mode)
Grid request based on
power (expert mode)
Grid request for connec-
tion power limit in kW (ex-
pert mode)
Grid request for discon-
nection power limit in kW
(expert mode)
Grid request based on
charge mode (expert
mode)
Description
Lower minimum threshold
of PV array voltage for
voltage monitoring in V
(expert mode)
Upper maximum thresh-
old of PV array voltage
for voltage monitoring
in V (expert mode, pro-
tected by
SMA Grid Guard)
Value
00:00:00 to
23:59:59
00:00:00 to
23:59:59
Disable
Enable
233.10 GdPwrStp to
300 kW
0 kW to
233.09 GdPwrStr
Off
Full
Equal
Both
Value
Explanation
172.5 V to
210.01 InvVtgNom
210.01 InvVt-
gNom to 264.5 V
SMA Solar Technology AG
Explanation
✖ ✓
✖ ✓
Disable
✖ ✓ Disable
Enable
✖ ✓ 4.0 kW
✖ ✓ 2.0 kW
Off
✖ ✓ Equal
Full charge
Equalization
charge
Full and
equalization
charge
✖ ✓ 172.50 V
✖ ✓ 250.0 V
Operating Manual
Default
Value
Default
Value

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunny island 6.0hSunny island 4.4mSunny island 8.0h

Table of Contents