SMA Solar Technology AG
235# Gen Start
No.
Name
235.01
GnAutoEna
235.02
GnAutoStr
235.03
GnSocTm1Str
235.04
GnSocTm1Stp
235.05
GnSocTm2Str
235.06
GnSocTm2Stp
235.07
GnTm1Str
235.08
GnTm2Str
235.09
GnPwrEna
Operating Manual
Description
Automatic restart of gen-
erator in the event of dis-
turbance
Number of attempts to
carry out automatic
restart of generator (ex-
pert mode)
Battery state of charge
limit for generator re-
quest in the standard ad-
ditional time period as %
This is the valid threshold
without the additional
time period.
Battery state of charge
limit for end of generator
request in the standard
additional time period as
%
This is the valid threshold
without the additional
time period.
Battery state of charge
limit for generator re-
quest in additional time
period as %
Battery state of charge
limit for end of generator
request in the additional
time period as %
Start time of the standard
additional time period
for generator request in
hh:mm:ss; corresponds to
the end time of the addi-
tional time period
Start time of additional
time period for generator
request in hh:mm:ss
Generator request based
on power (expert mode)
13 Parameters in Sunny Remote Control
Value
Explanation
Off
Disable
On
Enable
0 to 10
1% to 235.04
GnSocTm1Stp
235.03
GnSocTm1Str to
95%
1% to 235.06
GnSocTm2Stp
235.05
GnSocTm2Str to
95%
00:00:00 to
23:59:59
00:00:00 to
23:59:59
Disable
Disable
Enable
Enable
SI30M-44M-60H-80H-BE-en-33
Default
Value
✖ ✓ On
✖ ✓ 3
✖ ✓ 40 %
✖ ✓ 80 %
✖ ✓ 40 %
✖ ✓ 80 %
✖ ✓ 00:00:00
✖ ✓ 00:00:00
✖ ✓ Enable