10 Troubleshooting
No.
Name
W 753 DateInvalid
F 754 BoxCom
W 755 LoBatMod1
W 756 LoBatMod2
W 757 LoBatMod3
F 758 McNoVtg
W 759 McNoVtgSv1
W 760 McNoVtgSlv2
W 778 DSPNoSlv1
W 779 DSPNoSlv2
F 781 SlvError
F 782 AIVtgMonFail
72
SI30M-44M-60H-80H-BE-en-33
Level Cause
1
Invalid date: System time is in-
valid.
2
Communication with MC
BOX is interrupted: Communi-
cation with Multicluster-Box is in-
terrupted.
1
Battery protection mode 1 is ac-
tivated.
1
Battery protection mode 2 is ac-
tivated.
1
Battery protection mode 3 is ac-
tivated.
2
Voltage of the main cluster can-
not be measured at L1 (Master).
1
Voltage of the main cluster can-
not be measured at L2 (slave 1).
1
Voltage of the main cluster can-
not be measured at L3 (slave 2).
1
CAN communication with
slave 1 is faulty.
1
CAN communication with
slave 2 is faulty.
4
Error at a slave in the main clus-
ter causing system shutdown.
4
Non-compliance of monitoring
times (islanding detection) and
external grid voltage in the de-
vice at L1 (Master)
SMA Solar Technology AG
Corrective measures
• Select the parameter 250.02 Dt
and set the date. Select the
parameter 250.03 Tm and set the
time.
• Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
• Ensure that the communication bus
is equipped with a terminator at
both ends.
• Disconnect the loads, start the
generator, start the Sunny Island
and charge the battery.
• Ensure that all circuit breakers of
the Sunny Island inverters in the
Multicluster-Box are closed.
• Ensure that the cabling at
connection AC1 is correctly
installed.
• Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
• Ensure that the communication bus
is equipped with a terminator at
both ends.
Read off the pending and logged warn-
ings and errors and eliminate the
causes.
• Contact the Service (see Section 16