13 Parameters in Sunny Remote Control
No.
Name
221.05
BatTmpStr
221.06
BatWirRes
221.07
BatFanTmpStr
222# Chargemode
No.
Name
222.01
BatChrgCurMax
222.02
AptTmBoost
222.03
AptTmFul
222.04
AptTmEqu
222.05
CycTmFul
222.06
CycTmEqu
222.07
ChrgVtgBoost
222.08
ChrgVtgFul
126
SI30M-44M-60H-80H-BE-en-33
Description
Battery temperature as
connection limit after
overtemperature discon-
nection in °C (expert
mode)
Cable resistance of the
battery connection, in mΩ
(expert mode)
Temperature limit for multi-
function relay with battery
room fan (BatFan func-
tion) in °C
Description
Maximum battery charg-
ing current in A
Absorption time of the
boost charge in minutes
(expert mode)
Absorption time for full
charge in hours (expert
mode)
Absorption time for
equalization charge in-
 hours (expert mode)
Cycle time of full charge
in days (expert mode)
Cycle time of equaliza-
tion charge in days (ex-
pert mode)
Setpoint of the cell volt-
age at boost charge in V
(expert mode)
Cell voltage setpoint for
full charge in V (expert
mode)
Value
Explanation
0°C to
221.04 BatTmpMax
0 mΩ to 100 mΩ
20°C to
221.04 BatTmpMax
Value
Explanation
10 A to 900 A
1 min to 600 min
For VRLA
For FLA
1.0 h to 20.0 h
1.0 h to 48.0 h
1 d to 180 d
7 d to 365 d
2.20 V to 2.70 V
VRLA
FLA, off-grid
FLA, on-grid
2.30 V to 2.70 V
Off-grid
On Grid
SMA Solar Technology AG
Default
Value
✓ ✓ 35°C
✓ ✓ 0 mΩ
✓ ✓ 40°C
Default
Value
✓ ✓ –
✓ ✓ 180 min
90 min
✓ ✓ 6.0 h
✓ ✓ 12.0 h
✓ ✓ 14 d
✓ ✓ 90 d
✓ ✓ 2.40 V
✖ ✓ 2.40 V
✓ ✖ 2.55 V
✖ ✓ 2.45 V
✓ ✖ 2.50 V
Operating Manual