Settings; Information List - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

2.13.3 Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr.
Parameter
3201
FORWARD POWER
3202
Pf<
3203
T-Pf<
3204
Pf>
3205
T-Pf>
3206A
MEAS. METHOD

2.13.4 Information List

No.
Information
5113
>Pf BLOCK
5116
>Pf< BLOCK
5117
>Pf> BLOCK
5121
Pf OFF
5122
Pf BLOCKED
5123
Pf ACTIVE
5126
Pf< picked up
5127
Pf> picked up
5128
Pf< TRIP
5129
Pf> TRIP
7UM61 Manual
C53000-G1176-C127-3
Setting Options
OFF
ON
Block relay
0.5 .. 120.0 %
0.00 .. 60.00 sec; ∞
1.0 .. 120.0 %
0.00 .. 60.00 sec; ∞
accurate
fast
Type of In-
formation
EM
>BLOCK forward power supervision
EM
>BLOCK forw. power superv. Pf< stage
EM
>BLOCK forw. power superv. Pf> stage
AM
Forward power supervis. is switched OFF
AM
Forward power supervision is BLOCKED
AM
Forward power supervision is ACTIVE
AM
Forward power: Pf< stage picked up
AM
Forward power: Pf> stage picked up
AM
Forward power: Pf< stage TRIP
AM
Forward power: Pf> stage TRIP
2.13 Forward Active Power Supervision (ANSI 32F)
Default Setting
OFF
Forward Power Supervision
9.7 %
P-forw.< Supervision Pickup
10.00 sec
T-P-forw.< Time Delay
96.6 %
P-forw.> Supervision Pickup
10.00 sec
T-P-forw.> Time Delay
accurate
Method of Operation
Comments
Comments