2.7 Definite-Time Overcurrent Protection (I>>, ANSI 50, 51, 67) with Direction Detection
2.7.3
Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
1301
O/C I>>
1302
I>>
1303
T I>>
1304
Phase Direction
1305
LINE ANGLE
2.7.4
Information List
No.
Information
1720
>BLOCK dir.
1721
>BLOCK I>>
1801
I>> Fault L1
1802
I>> Fault L2
1803
I>> Fault L3
1806
I>> forward
1807
I>> backward
1808
I>> picked up
1809
I>> TRIP
1955
I>> OFF
1956
I>> BLOCKED
1957
I>> ACTIVE
7UM61 Manual
C53000-G1176-C127-3
C
Setting Options
OFF
ON
Block relay
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
0.00 .. 60.00 sec; ∞
Forward
Reverse
-90 .. 90 °
Type of In-
formation
EM
>BLOCK direction I>> stage
EM
>BLOCK I>>
AM
O/C fault detection stage I>> phase L1
AM
O/C fault detection stage I>> phase L2
AM
O/C fault detection stage I>> phase L3
AM
O/C I>> direction forward
AM
O/C I>> direction backward
AM
O/C prot. I>> picked up
AM
O/C I>> TRIP
AM
O/C prot. stage I>> is switched OFF
AM
O/C prot. stage I>> is BLOCKED
AM
O/C prot. stage I>> is ACTIVE
Default Setting
OFF
Overcurrent Time Protec-
tion I>>
4.30 A
I>> Pickup
21.50 A
0.10 sec
T I>> Time Delay
Reverse
Phase Direction
60 °
Line Angle
Comments
Comments
51