Siemens Siprotec 7UM611 Manual page 390

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
9112A
RTD11 LOCATION
9113
RTD11 STAGE 1
9114
RTD11 STAGE 1
9115
RTD11 STAGE 2
9116
RTD11 STAGE 2
9121A
RTD12 TYPE
9122A
RTD12 LOCATION
9123
RTD12 STAGE 1
9124
RTD12 STAGE 1
9125
RTD12 STAGE 2
9126
RTD12 STAGE 2
390
Function
C
Setting Options
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
Default Setting
Other
RTD11: Location
100 °C
RTD11: Temperature Stage 1
Pickup
212 °F
RTD11: Temperature Stage 1
Pickup
120 °C
RTD11: Temperature Stage 2
Pickup
248 °F
RTD11: Temperature Stage 2
Pickup
Not connected
RTD12: Type
Other
RTD12: Location
100 °C
RTD12: Temperature Stage 1
Pickup
212 °F
RTD12: Temperature Stage 1
Pickup
120 °C
RTD12: Temperature Stage 2
Pickup
248 °F
RTD12: Temperature Stage 2
Pickup
C53000-G1176-C127-3