3 Mounting and Commissioning
For devices up to release 7UM61.../BB check the jumpers for the set nominal voltage
of the integrated power supply according to Table 3-1, the quiescent state of the life
contact according to Table 3-2 and the selected pickup voltages of the binary inputs
BI1 through BI7 according to Table 3-3.
Table 3-1
Table 3-2
Table 3-3
1)
2)
242
Jumper settings for nominal voltage of the integrated power supply on the pro-
cessor printed circuit board B–CPU for 7UM61.../BB
Jumper
60/110/125 VDC
X51
1–2
X52
1–2 and 3–4
X53
1–2
Jumper setting for the quiescent state of the life contact on the B–CPU proces-
sor PCB for 7UM61.../BB
Jumper
Open in the quiescent
state
X40
1–2
Jumper settings for the control voltages of binary inputs BI1 through BI7 on the
B–CPU processor PCB for 7UM61.../BB
Binary Inputs
Jumper
BI1
BI2
BI3
BI4
BI5
BI6
BI7
Factory settings for devices with rated power supply voltages 24 VDC to 125 VDC
Factory settings for devices with rated power supply voltages 110 VDC to 220 VDC and
115/230 VAC
Rated voltage
110/125/220/250 V DC
115 V AC
2–3
2–3
2–3
interchangeable
Closed in the quiescent
state
2–3
19 V Threshold
X21
L
X22
L
X23
L
X24
L
X25
L
X26
L
X27
L
24/48 VDC
Jumpers
X51 to X53
Not used
cannot be changed
Presetting
2–3
1)
2)
88 V Threshold
H
H
H
H
H
H
H
7UM61 Manual
C53000-G1176-C127-3