Communication Interfaces - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

Output Relays
LEDs
4.1.4

Communication Interfaces

Operating Interface
7UM61 Manual
C53000-G1176-C127-3
1
Indication/command relay
Number:
Make/break capacity
Switching Voltage
admissible current per contact
admissible total current on common
path contacts
1
) UL–listed with the following nominal values:
Number
RUN (green)
ERROR (red)
allocatable LEDs (red)
Connection
Operation
Transmission Speed
bridgeable distance
)
7UM611*–
7UM612*–
MAKE
BREAK
250 V
5 A continuous 30 A for 0.5 s
5 A continuous 30 A ≤ 0.5 s
120 V AC
240 V AC
240 V AC
24 V DC
48 V DC
240 V DC
120 V AC
240 V AC
1
1
7UM611
7
front side, non-isolated, RS 232, 9-pin DSUB socket
for connecting a PC
®
with DIGSI
4
min. 4 800 Baud; max. 115 200 Baud
Factory Setting: 38 400 Baud; Parity: 8E1
15 m
4.1 General
11 (each with 1 NO contact)
19 (each with 1 NO contact)
1000 W/VA
30 VA
40 W resistive
25 W at L/R ≤ 50 ms
Pilot duty, B300
Pilot duty, B300
5 A General Purpose
5 A General Purpose
0.8 A General Purpose
0.1 A General Purpose
1/6 hp (4.4 FLA)
1/2 hp (4.9 FLA)
7UM612
14
297