Siemens Siprotec 7UM611 Manual page 24

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

1 Introduction
Negative Sequence
• Precise evaluation of negative sequence component of the three phase currents.
Protection
• Alarm stage when a set unbalanced load is exceeded.
• Thermal characteristic with adjustable negative sequence factor and adjustable
• High-speed trip stage for large unbalanced loads (can be used for short-circuit pro-
Underexcitation
• Conductance measurement from positive sequence components.
protection
• Multi-step characteristic for steady-state and dynamic stability limits;
• Consideration of excitation voltage (only via binary input).
Reverse Power Pro-
• Calculation of power from positive sequence components.
tection
• Highly sensitive and precise active power measurement (detection of small motor-
• Insensitive to power fluctuations.
• Long-time stage and short-time stage (active with closed emergency tripping valve).
Forward Power Su-
• Calculation of power from positive sequence components.
pervision
• Supervision of over-power (P>) and/or under-power (P<) of active power output
• Optionally high-speed or high-accuracy measurement.
Impedance protec-
• Overcurrent pickup with undervoltage seal-in (for synchronous machines which
tion
• 2 impedance zones, 1 overreach zone (switchable via binary input), 4 time stages.
• Polygonal tripping characteristics;
Undervoltage Pro-
• Two-stage undervoltage measurement of positive sequence component of voltag-
tection
Overvoltage Pro-
• Two-stage overvoltage measurement of the highest of the three voltages.
tection
Frequency Protec-
• Monitoring on undershooting (f<) and/or overshooting (f>) with 4 frequency limits
tion
• Insensitive to harmonics and abrupt phase angle changes.
• Settable undervoltage threshold.
Overexcitation Pro-
• Calculation of the ratio U/f.
tection
• Adjustable warning and tripping stage.
• Standard characteristic or arbitrary trip characteristic for calculation of the thermal
24
cooldown time.
tection).
ing powers even with low power factor cos ϕ , angle error compensation).
with individually adjustable power limits.
take their excitation voltage from the terminals).
es.
Optionally with phase-to-phase voltages or phase-to-earth voltages.
and delay times that are independently adjustable.
stress, selectable.
7UM61 Manual
C53000-G1176-C127-3