Settings; Information List - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

2.15.3 Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
Addr.
Parameter
4001
UNDERVOLTAGE
4002
U<
4003
T U<
4004
U<<
4005
T U<<
4006A
DOUT RATIO

2.15.4 Information List

No.
Information
6503
>BLOCK U/V
6506
>BLOCK U<
6508
>BLOCK U<<
6530
Undervolt. OFF
6531
Undervolt. BLK
6532
Undervolt. ACT
6533
U< picked up
6537
U<< picked up
6539
U< TRIP
6540
U<< TRIP
7UM61 Manual
C53000-G1176-C127-3
Setting Options
OFF
ON
Block relay
10.0 .. 125.0 V
0.00 .. 60.00 sec; ∞
10.0 .. 125.0 V
0.00 .. 60.00 sec; ∞
1.01 .. 1.20
Type of In-
formation
EM
>BLOCK undervoltage protection
EM
>BLOCK undervoltage protection U<
EM
>BLOCK undervoltage protection U<<
AM
Undervoltage protection switched OFF
AM
Undervoltage protection is BLOCKED
AM
Undervoltage protection is ACTIVE
AM
Undervoltage U< picked up
AM
Undervoltage U<< picked up
AM
Undervoltage U< TRIP
AM
Undervoltage U<< TRIP
2.15 Undervoltage Protection (ANSI 27)
Default Setting
OFF
Undervoltage Protection
75.0 V
U< Pickup
3.00 sec
T U< Time Delay
65.0 V
U<< Pickup
0.50 sec
T U<< Time Delay
1.05
U<, U<< Drop Out Ratio
Comments