Siemens Siprotec 7UM611 Manual page 177

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

circuit has been interrupted, a short-circuit exists in the trip circuit, battery voltage
failure occurs, or malfunctions occur with the circuit breaker mechanism. Accordingly
it is used as monitoring criterion.
Table 2-8
No.
Trip contact
1
Open
2
Open
3
Closed
4
Closed
The conditions of the two binary inputs are scanned periodically. A query takes place
about every 600 ms. If three consecutive conditional checks detect an abnormality
(after 1.8 s), an annunciation is reported (see the following figure). The repeated mea-
surements help to determine the delay of the alarm message and to avoid that an
alarm is output during short-time transition periods. After the fault in the trip circuit is
removed, the alarm is reset automatically after the same time.
Figure 2-68
Monitoring with
If two binary inputs connected to common potential are used, they are connected ac-
Two Binary Inputs
cording to Figure 2-67, to L+ or once in parallel with the corresponding protection
(connected to
command relay contact and to the circuit breaker auxiliary contact 1.
common potential)
Figure 2-69
7UM61 Manual
C53000-G1176-C127-3
Condition Table for Binary Inputs, Depending on RTC and CB Position
Circuit breaker
AuxCont 1
TRIP
Closed
CLOSE
Open
TRIP
Closed
CLOSE
Open
Logic diagram of the trip circuit supervision with two binary inputs
Principle of Trip Circuit Monitor with Two Binary Inputs (connected to common
potential)
2.29 Trip Circuit Supervision
AuxCont 2
BI 1
Open
H
Closed
H
Open
L
Closed
L
BI 2
L
H
L
H
177