In addition, the following are be available:
Minimum and
Minimum and maximum values for the positive-sequence components I
Maximum Values
active power P, reactive power Q, in primary values, of the frequency f and of the 3rd
harmonic content in the displacement voltage in secondary values U
the date and time they were last updated. The minimum/maximum values can be reset
via binary inputs or, in the delivery status of the device, also via the F4 function key.
Minimum and Maximum Values: only with version 7UM61**
Power Metered
W
Values
gawatt hours primary or in kVARh, MVARh or GVARh primary, separately according to
the input (+) and output (–), or capacitive and inductive.
The calculation of the operational measured values is also executed during fault. The
values are updated at intervals of ≥ 0.3 s and ≤ 1 s.
Power Metered Values: only with version 7UM61**
Transfer of Mea-
Measured values can be transferred via the interfaces to a central control and storage
sured Values
system.
Definition of Power Measurement
The 7UM61 uses the generator reference-arrow system. The power output is positive.
Figure 2-80
The following table shows the operating ranges for synchronous and asynchronous
machines. For this, parameter 1108 ACTIVE POWER is set to Generator. "Normal
condition" shows the power under normal operating conditions: + means that a posi-
tive power is displayed on the protective device, – means that the power is negative.
7UM61 Manual
C53000-G1176-C127-3
, W
, metered values of the active and reactive energy in kilowatt, megawatt or gi-
p
q
Definition of Positive Direction of Reference Arrows
2.35 Ancillary Functions
and U
1
. Included are
3.H
_
_
*****
3***
_
_
*****
3***
, the
1
213