Siemens Siprotec 7UM611 Manual page 169

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

Thereby I
factor BAL. FACTOR I represents the allowable asymmetry of the phase currents
while the limit value BALANCE I LIMIT is the lower limit of the operating range of
this monitoring (see the following figure). Both settings are adjustable. The dropout
ratio is about 95 %.
This malfunction is signaled as "Fail I balance".
Figure 2-64
Voltage Symmetry
From the phase-to-ground voltages, the rectified average value is formed as a check
for symmetry of absolute values. The smallest phase voltage is compared to the larg-
est. Asymmetry is recognised if
| U
Thereby U
factor BAL. FACTOR U is the measure for the asymmetry of the conductor voltages;
the limit BALANCE U-LIMIT is the lower limit of the operating range of this monitoring
(see following figure). Both settings are adjustable. The dropout ratio is about 95 %.
This malfunction is reported as "Fail U balance".
If the 90% stator earth fault protection functions are active, a zero voltage results on
voltage asymmetry. If this cause protection pickup, monitoring is relegated to the back-
ground and issues no indication.
Figure 2-65
7UM61 Manual
C53000-G1176-C127-3
is the largest of the three phase currents I
max
Current symmetry monitoring
| < BAL. FACTOR U as long as | U
| / | U
min
max
is the highest of the three voltages and U
max
Voltage symmetry monitoring
2.28 Measurement Supervision
the smallest. The symmetry
min
| > BALANCE U-LIMIT
max
the smallest. The symmetry
min
169