Frequency Protection (Ansi 81) - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

4.12

Frequency Protection (ANSI 81)

Setting Ranges / Increments
Times
Dropout Difference
Dropout Ratio
Tolerances
Influencing Variables
7UM61 Manual
C53000-G1176-C127-3
Number of Frequency Elements
Pickup Frequency f> or f<
Delay Times
T f1
T f2 to T f4
Undervoltage Blocking
(Positive Sequence Component U
The set times are pure delay times.
Pickup Times f>, f<
Dropout Times f>, f<
f = I Pickup Value – Dropout Value I
Dropout Ratio for Undervoltage Blocking
Frequencies f>, f<
Undervoltage Blocking
Time Delays T(f<, f<)
Power Supply DC Voltage in Range
0.8 ≤ U
≤ 1.15
/U
PS
PSN
Temperature in Range
23°F or –5 °C ≤ Θ
≤ 131°F or 55 °C
amb
Harmonics
- Up to 10 % 3rd harmonic
- Up to 10 % 5th harmonic
4.12 Frequency Protection (ANSI 81)
4; can be set to f> or f<
40 Hz to 65.00 Hz
0.00 s to 600.00 s
0.00 s to 100.00 s
10.0 V to 125.0 V and 0 V
)
(no blocking)
1
approx. 100 ms
approx. 100 ms
approx. 20 mHz
approx. 1.05
10 mHz (at U = U
1 % of setting value or 0.5 V
1 % of setting value or 10 ms
1 %
0.5 %/10 K
1 %
1 %
Increments 0.01 Hz
Increments 0.01 s
Increments 0.01 s
Increments 0.1V
, f = f
)
N
N
325