2 Functions
Parameter 104 FAULT VALUE is used to specify whether the oscillographic fault re-
cording should record Instant. values or RMS values. If RMS values is stored,
the available recording time increases by the factor 16.
For the high-current stage I>> of the overcurrent protection, address 113O/C PROT.
I>> determines whether Non-Directional or directional is to be operative. By
selecting Disabled, this overcurrent stage can be excluded altogether. With inverse
time overcurrent protection 114O/C PROT. Ip, depending on the ordered variant,
various characteristics are available for selection, in accordance with IEC or ANSI
standard. Selecting 'disabled' deconfigures inverse time overcurrent protection.
For earth fault protection, Address 150 S/E/F PROT. presents the options non-
dir. U0, non-dir. U0&I0 and directional, unless the whole function is
Disabled. The first option evaluates only the displacement voltage (to be used with
unit connection). The second option evaluates in addition to the displacement voltage,
the magnitude of the earth fault current (or the difference between the starpoint current
and the total current of a toroidal CT in busbar systems with low-ohmic switchable star-
point resistors). The third option considers as a further criterion the direction of the
earth fault current if with machines in busbar connection the magnitudes of displace-
ment voltage and earth fault current alone are not sufficient to distinguish between
system earth faults and machine earth faults.
For trip circuit monitoring, address 182 Trip Cir. Sup. is used to specify whether
two binary inputs (2 Binary Inputs) or only one (1 Binary Input) should be
utilized.
2.2.3

Settings

Addr.
Parameter
103
Grp Chge OPTION
104
FAULT VALUE
112
O/C PROT. I>
113
O/C PROT. I>>
114
O/C PROT. Ip
116
Therm.Overload
117
UNBALANCE LOAD
130
UNDEREXCIT.
131
REVERSE POWER
132
FORWARD POWER
133
IMPEDANCE PROT.
32
Setting Options
Disabled
Enabled
Disabled
Instant. values
RMS values
Disabled
Enabled
Disabled
directional
Non-Directional
Disabled
with IEC
with ANSI
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Default Setting
Disabled
Setting Group Change Option
Instant. values
Fault values
Enabled
Overcurrent Protection I>
Non-Directional
Overcurrent Protection I>>
Disabled
Inverse O/C Time Protection
Enabled
Thermal Overload Protection
Enabled
Unbalance Load (Negative Se-
quence)
Enabled
Underexcitation Protection
Enabled
Reverse Power Protection
Enabled
Forward Power Supervision
Enabled
Impedance Protection
Comments
7UM61 Manual
C53000-G1176-C127-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7um612

Table of Contents