Motor Starting Time Supervision (Ansi 48) - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

4.19

Motor Starting Time Supervision (ANSI 48)

Setting Ranges / Increments
Tripping Characteristic
Dropout Ratio
Tolerances
Influencing Variables for Pickup Values
7UM61 Manual
C53000-G1176-C127-3
Motor Startup Current
I
STARTUP
Pickup Threshold for Startup
Detection
I
STRT DETECT.
Maximum Startup Time
T
Max. STARTUP
Admissible Locked Rotor Time
T
LOCKED-ROTOR
I
/I
rms
STARTUP DETECT.
Pickup Threshold
Time Delay
Power Supply DC Voltage in Range
0,8 ≤ U
≤ 1.15
/U
PS
PSN
Temperature in Range
23°F or –5 °C ≤ Θ
≤ 131°F or 55 °C
amb
Frequency in Range
0,95 ≤ f/f
≤ 1.05
N
Harmonics
- Up to 10 % 3rd harmonic
- Up to 10 % 5th harmonic
4.19 Motor Starting Time Supervision (ANSI 48)
for I
= 1 A
0.10 A to 16.00 A
N
for I
= 5 A
0.50 A to 80.00 A
N
for I
= 1 A
0.60 A to 10.0 A
N
for I
= 5 A
3.00 A to 50.00 A
N
1.0 s to 180.0 s
0.05 s to 120.0 s or ∞ (in-
effective)
approx. 0.95
for I
= 1 A
1 % of setting value or 10 mA
N
for I
= 5 A
1 % of setting value or 50 mA
N
5 % or 30 ms
≤ 1 %
≤ 0.5 % / 10 K
≤ 1 %
≤ 1 %
≤ 1 %
Increments 0.01 A
Increments 0.05 A
Increments 0.01 A
Increments 0.05 A
Increments 0.1 s
Increments 0.1 s
333

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siprotec 7um612

Table of Contents