4.15

Jump of Voltage Vector

Setting Ranges / Increments
Times
Dropout Ratios
Tolerances
Influencing Variables
7UM61 Manual
C53000-G1176-C127-3
Stage ∆
ϕ
Delay Time T
Reset Time T
Reset
Undervoltage Blocking U1>
Pickup Times ∆
ϕ
Dropout Times ∆
ϕ
Angle Jump
Undervoltage Blocking
Delay times T
Power Supply DC Voltage in Range
0.8 ≤ U
≤ 1.15
/U
PS
PSN
Temperature in Range
23°F or –5 °C ≤ Θ
≤ 131°F or 55 °C
amb
Frequency in Range
0.95 ≤ f/f
≤ 1.05
N
Harmonics
- Up to 10 % 3rd harmonic
- Up to 10 % 5th harmonic
4.15 Jump of Voltage Vector
2° to 30°
0.00 to 60.00 s
0.00 to 60.00 s
10.0 to 125.0 V
approx. 75 ms
approx. 75 ms
0.5° at U > 0.5 U
N
1 % of setting value or 0.5 V
1 % or 10 ms
≤ 1 %
≤ 0.5 % / 10 K
≤ 1 %
≤ 1 %
≤ 1 %
Increments 1°
Increments 0.01 s
or ineffective
Increments 0.01 s
or ineffective
Increments 0.1V
329