Binary Inputs And Outputs - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

4 Technical Data
AC Voltage
4.1.3

Binary Inputs and Outputs

Binary Inputs
296
7UM611
7UM612
Bridging time on failure or short circuit
Voltage supply using integrated converter
Nominal Auxiliary AC Voltage U
admissible voltage ranges
Quiescent power consumption
Quiescent power consumption
Bridging time on failure or short circuit
Variant
7UM611*–
7UM612*–
Rated Voltage Range
Current Consumption, Energized
Switching Thresholds
Binary Inputs BI1 to BI7
for rated voltages
for rated voltages
Binary Inputs BI8 to BI15
for rated voltages
for rated voltages
for rated voltages
Maximum admissible voltage
Input Impulse suppression
energized
≥ 50 ms at V ≥ 110 V DC
≥ 20 ms at V ≥ 24 V DC
115 VAC (50/60 Hz)
Aux
92 to 132 V AC
approx. 4 VA
approx. 12 VA
≥ 200 ms
Number
7 (configurable)
15 (configurable)
24 V DC to 250 V DC, bipolar
approx. 1.8 mA, independent of control voltage
adjustable with jumpers
24/48/
60/110/125 V DC
110/125/
220/250 V DC
24/48/
60/110/125 V DC
110/125/
220/250 V DC
220/250 V DC
300 V DC
220 nF coupling capacity at 220 V with recovery
time > 60 ms
approx. 9.5 W
approx. 12.5 W
230 V AC (50/60 Hz)
184 to 265 V AC
≥ 19 V DC
U
high
≤ 10 V DC
U
low
≥ 88 V DC
U
high
≤ 44 V DC
U
low
≥ 19 V DC
U
high
≤ 10 V DC
U
low
≥ 88 V DC
U
high
≤ 44 V DC
U
low
≥ 176 V DC
U
high
≤ 88 V DC
U
low
7UM61 Manual
C53000-G1176-C127-3