2.18.3 Settings

Addr.
Parameter
4301
OVEREXC. PROT.
4302
U/f >
4303
T U/f >
4304
U/f >>
4305
T U/f >>
4306
t(U/f=1.05)
4307
t(U/f=1.10)
4308
t(U/f=1.15)
4309
t(U/f=1.20)
4310
t(U/f=1.25)
4311
t(U/f=1.30)
4312
t(U/f=1.35)
4313
t(U/f=1.40)
4314
T COOL DOWN

2.18.4 Information List

No.
Information
5353
>U/f BLOCK
5357
>RM th.rep. U/f
5361
U/f> OFF
5362
U/f> BLOCKED
5363
U/f> ACTIVE
5367
U/f> warn
5369
RM th.rep. U/f
5370
U/f> picked up
5371
U/f>> TRIP
5372
U/f> th.TRIP
5373
U/f>> pick.up
7UM61 Manual
C53000-G1176-C127-3
2.18 Overexcitation (Volt/Hertz) Protection (ANSI 24)
Setting Options
OFF
ON
Block relay
1.00 .. 1.20
0.00 .. 60.00 sec; ∞
1.00 .. 1.40
0.00 .. 60.00 sec; ∞
0 .. 20000 sec
0 .. 20000 sec
0 .. 20000 sec
0 .. 20000 sec
0 .. 20000 sec
0 .. 20000 sec
0 .. 20000 sec
0 .. 20000 sec
0 .. 20000 sec
Type of In-
formation
EM
>BLOCK overexcitation protection
EM
>Reset memory of thermal replica U/f
AM
Overexcitation prot. is swiched OFF
AM
Overexcitation prot. is BLOCKED
AM
Overexcitation prot. is ACTIVE
AM
Overexc. prot.: U/f warning stage
AM
Reset memory of thermal replica U/f
AM
Overexc. prot.: U/f> picked up
AM
Overexc. prot.: TRIP of U/f>> stage
AM
Overexc. prot.: TRIP of th. stage
AM
Overexc. prot.: U/f>> picked up
Default Setting
OFF
Overexcitation Protection (U/f)
1.10
U/f > Pickup
10.00 sec
T U/f > Time Delay
1.40
U/f >> Pickup
1.00 sec
T U/f >> Time Delay
20000 sec
U/f = 1.05 Time Delay
6000 sec
U/f = 1.10 Time Delay
240 sec
U/f = 1.15 Time Delay
60 sec
U/f = 1.20 Time Delay
30 sec
U/f = 1.25 Time Delay
19 sec
U/f = 1.30 Time Delay
13 sec
U/f = 1.35 Time Delay
10 sec
U/f = 1.40 Time Delay
3600 sec
Time for Cooling Down