Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

Rate-of-Frequency-
• Monitors whether the frequency overshoots (df/dt>) and/or undershoots (df/dt<) a
Change Protection
• Variable measuring windows
• Coupling to frequency protection pickup.
• Settable undervoltage threshold.
Vector Jump
• Sensitive phase jump detection to be used for network disconnection.
90% Stator Earth
• Suitable for generators in unit connection and directly connected to busbars.
Fault Protection
• Measurement of displacement voltage via the neutral or earthing transformer or by
• Highly sensitive earth current detection, optional with or without directional determi-
• Directional characteristic adjustable.
• Determination of the earth-faulted phase.
Sensitive Earth
• Two-stage earth fault current measurement: I
Fault Protection
• High sensitivity (adjustable on the secondary side from 2 mA).
• Can be used for stator earth fault or rotor earth fault detection.
• Measurement circuit monitoring for minimum current flow when used for rotor earth
100% Stator Earth
• Detection of the 3rd harmonic of the voltage at the starpoint or broken delta winding
Fault Protection
with 3rd Harmonic
• In addition to the 90-%-stator earth fault protection there is a protection of the entire
Motor Starting Time
• Inverse time overcurrent tripping based on an evaluation of the motor starting
Supervision
• Inverse time delay with blocked rotor.
Restart Inhibit for
• Approximate computation of rotor overtemperature.
Motors
• Motor switchon is enabled only a if a restartup limit is undershot.
• Calculation of waiting time until automatic reclosure is enabled.
• Different prolongation of cooldown time constants for standstill/operation period is
• Possibility for disabling the start inhibit if emergency startup is required.
Breaker Failure
• By checking the current or evaluation of the breaker auxiliary contacts.
Protection
• Initiation of each integrated protection function allocated to the circuit breaker.
• Initiation possible through a binary input from an external protective device.
7UM61 Manual
C53000-G1176-C127-3
set limit value, with 4 individually settable limit values or delay times.
calculation from phase-to-earth voltages.
nation with zero sequence components (I
fault protection.
of an earthing transformer.
stator winding (protective range 100 %).
current
taken into consideration.
1.3 Characteristics
, U
).
0
0
>> and I
>.
EE
EE
25