Information List - Siemens Siprotec 7UM611 Manual

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

Addr.
Parameter
9121A
RTD12 TYPE
9122A
RTD12 LOCATION
9123
RTD12 STAGE 1
9124
RTD12 STAGE 1
9125
RTD12 STAGE 2
9126
RTD12 STAGE 2

2.32.4 Information List

No.
Information
14101
Fail: RTD
14111
Fail: RTD 1
14112
RTD 1 St.1 p.up
14113
RTD 1 St.2 p.up
14121
Fail: RTD 2
14122
RTD 2 St.1 p.up
14123
RTD 2 St.2 p.up
14131
Fail: RTD 3
14132
RTD 3 St.1 p.up
14133
RTD 3 St.2 p.up
14141
Fail: RTD 4
14142
RTD 4 St.1 p.up
14143
RTD 4 St.2 p.up
14151
Fail: RTD 5
14152
RTD 5 St.1 p.up
14153
RTD 5 St.2 p.up
14161
Fail: RTD 6
14162
RTD 6 St.1 p.up
14163
RTD 6 St.2 p.up
14171
Fail: RTD 7
14172
RTD 7 St.1 p.up
14173
RTD 7 St.2 p.up
14181
Fail: RTD 8
14182
RTD 8 St.1 p.up
7UM61 Manual
C53000-G1176-C127-3
Setting Options
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Type of In-
formation
AM
Fail: RTD (broken wire/shorted)
AM
Fail: RTD 1 (broken wire/shorted)
AM
RTD 1 Temperature stage 1 picked up
AM
RTD 1 Temperature stage 2 picked up
AM
Fail: RTD 2 (broken wire/shorted)
AM
RTD 2 Temperature stage 1 picked up
AM
RTD 2 Temperature stage 2 picked up
AM
Fail: RTD 3 (broken wire/shorted)
AM
RTD 3 Temperature stage 1 picked up
AM
RTD 3 Temperature stage 2 picked up
AM
Fail: RTD 4 (broken wire/shorted)
AM
RTD 4 Temperature stage 1 picked up
AM
RTD 4 Temperature stage 2 picked up
AM
Fail: RTD 5 (broken wire/shorted)
AM
RTD 5 Temperature stage 1 picked up
AM
RTD 5 Temperature stage 2 picked up
AM
Fail: RTD 6 (broken wire/shorted)
AM
RTD 6 Temperature stage 1 picked up
AM
RTD 6 Temperature stage 2 picked up
AM
Fail: RTD 7 (broken wire/shorted)
AM
RTD 7 Temperature stage 1 picked up
AM
RTD 7 Temperature stage 2 picked up
AM
Fail: RTD 8 (broken wire/shorted)
AM
RTD 8 Temperature stage 1 picked up
Default Setting
Not connected
RTD12: Type
Other
RTD12: Location
100 °C
RTD12: Temperature Stage 1
Pickup
212 °F
RTD12: Temperature Stage 1
Pickup
120 °C
RTD12: Temperature Stage 2
Pickup
248 °F
RTD12: Temperature Stage 2
Pickup
Comments
2.32 RTD-Box
Comments
199