Siemens Siprotec 7UM611 Manual page 167

Multi-functional generator protection relay 7um61 series
Table of Contents

Advertisement

Measurement Value
In the current paths there are three input transformers; the digitized sum of the trans-
Acquisition – Cur-
former currents of one side must be almost zero for generators with isolated starpoint
rents
during earth-fault-free operation. A current circuit fault is detected if
I
ΣI THRESHOLD and ΣI FACTOR are programmable settings. The component ΣI
FACTOR · Imax takes into account the admissible current-proportional transformation
error of the input transformer, which can occur particularly when high fault current
levels are present (see the following figure). The dropout ratio is about 95 %.
This malfunction is signaled as "Failure Σ I".
The current sum monitoring is not executed if the starpoint was set as 273 at Power
System Data 1 (address low-resist.).
Figure 2-62
Measured Value Ac-
Four measuring inputs are available in the voltage path: If three of them are used for
quisition Voltages
phase-earth voltages, and one input for the displacement voltage (e–n voltage from
the broken delta winding or neutral transformer) of the same system, a fault in the
phase-earth voltage sum is detected if
| U
Here SUM.thres. U and SUM.Fact. U are parameter settings, and U
highest of the phase-earth voltages. Factor k
ferences between the displacement voltage input and the phase voltage inputs (pa-
rameter k
considers admissible voltage-proportional transformation errors of the input transduc-
ers, which can be especially large in the presence of high voltages (see the following
figure).
This malfunction is reported as "Fail Σ U Ph-E".
7UM61 Manual
C53000-G1176-C127-3
| > ΣI THRESHOLD · I
= | I
+ I
+ I
F
L1
L2
L3
Current sum monitoring
+ U
+ U
+ k
· U
L1
L2
L3
U
E
= Uph / Udelta Address 225). The SUM.Fact. U x U
U
+ ΣI FACTOR · I
N
| > SUM.thres. U + SUM.Fact. U x U
considers the transformation ratio dif-
U
2.28 Measurement Supervision
max
max
is the
max
component
max
167