4.12 Recommendations concerning the Power Supply and
Protection of the System
Instructions for Solving Possible Ground Return Problems
To avoid ground return signals from remote systems use the same phase for the dif-
ferent systems' power supply.
If the building's features make this impossible, use an intermediate transformer to
detach the external system so that damage may be avoided during operation.
Protective Ground Connection
Danger
!
The HiPath1130/1150/1190 power supplies must be protected by an earth ground in
a separate safety ground conductor (PE - green/yellow) (TN-S system, minimum sec-
tion = 2.5 mm
Any additional servicing of low voltage networks (100 - 240 V AC) must be done by
qualified technical personnel only.
Do not use as a grounding point:
- Central heating systems
- Sewer systems
- Ground wire for antennae systems.
Failure to comply with these recommendations may lead to hazardous conditions.
Example of a Power Supply Configuration for the HiPath1130/1150/1190 Systems
L1 N PE
127 Vac
Figure 4-32
4-42
Procedure
"Performing a Visual Inspection" on page 4-48.
Configure the required data (see "Operation" on page 6-1).
2
) as shown in Figure 4-32.
Diagram of Power Supply Configuration for the HiPath 1130/1150 Systems
For internal distribution only
HiPath1130/1150/1190
A31003-K1250-S100-12-7619
HiPath 1100, Service Manual