Alarm, error, and system messages
10.2 Diagnostics
10.2.4.10

Diagnostic value '12.PST - Monitoring of partial stroke test'

Indication on the display: • OFF
Purpose:
Description of indications
on the display:
Status messages:
Factory setting:
214
• C-ERR
• FdInI
• notSt
• ###.#
• SdtSt
• FdtSt
This diagnostics parameter indicates the stroke time measured
during the last partial stroke test.
A partial stroke test can be initiated manually or a current partial
stroke test can be interrupted by pressing the
• OFF: The partial stroke test function is deactivated.
• C-ERR: Configuration error. Partial stroke test cannot be
started. Settings in the 'A1.STPOS starting position',
'A3.STRKH stroke height' and 'A4.STRKD direction of stroke'
parameters are not plausible.
• FdInI - Failed PST Initialization: The reference stroke time
measurement of the partial stroke test has failed.
• notSt - No Test: A manual partial stroke test has not yet been
executed.
• ###.#: Corresponds to the measured stroke time in seconds.
The last partial stroke test was successfully executed.
• SdtSt - Stopped Test: The last partial stroke test was
interrupted.
• FdtSt - Failed Test: The last partial stroke test has failed.
The following status messages appear when you hold the
ton pressed:
• notoL - No Tolerance: The control valve is beyond the tolerance
range to start the partial stroke test. A manual partial stroke test
is not started.
• Strt - Start: A manual partial stroke test is started five seconds
after pressing the button.
• StoP - Stop: The current partial stroke test is interrupted. 'WAIT'
is output in the display.