Technical data
12.8 Option modules
12.8.8
External position detection system
12.8.8.1
Rated conditions for external position detection system
Ambient temperature
Perm. ambient temperature for operation
•
Degree of protection
1)
Climate class
Storage
•
Transport
•
Operation
•
) Impact energy max. 1 joule.
1
12.8.8.2
Construction for external position detection system
Construction
How does it work?
Range of stroke (linear actuator)
•
Angle of rotation (part-turn actuator)
•
Mounting method
On the linear actuator
•
On the part-turn actuator
•
Material
Enclosure
•
Weight, basic device
Torque for cable gland nut made of plastic
260
In hazardous areas, observe the maximum permissible
ambient temperature corresponding to the temperature
class.
-40 ... +90 °C (-40 ... +194 °F)
IP66 to IEC/EN 60529 / NEMA 4X
According to IEC/EN 60721-3
1K5, but -40 ... +90 °C (1K5, but -40 ... +194 °F)
2K4, but -40 ... +90 °C (2K4, but -40 ... +194 °F)
4K3, but -40 ... +90 °C (4K3, but -40 ... +194 °F)
3 ... 130 mm (0.12 ... 5.12") (angle of rotation of the posi-
tioner shaft 16 to 90°)
30 ... 100°
Using mounting kit 6DR4004-8V and, where necessary,
an additional lever arm 6DR4004-8L on actuators accord-
ing to IEC 60534-6-1 (NAMUR) with a fin, columns, or a
plane surface.
Using mounting kit 6DR4004-8D on actuators with mount-
ing plane according to VDI/VDE 3845 and IEC 60534-6-2:
The required mount must be provided on the actuator-
side.
Makrolon® glass-fiber reinforced polycarbonate (PC)
Approximately 0.9 kg (1.98 lb)
2.5 Nm
Operating Instructions, 02/2016, A5E00074631-AB
SIPART PS2 with and without HART