Parameter assignment
9.3 Tabular overview of the parameters
Overview parameter A
Parameter
Function
A. PST
Partial stroke test with the following parameters:
A1.STPOS
Start position
A2.STTOL
Start tolerance
A3.STRKH
Stroke height
A4.STRKD
Stroke direction
A5.RPMD
Ramp mode
A9.PSTIN
Reference stroke time for partial stroke test
Overview parameter b
Parameter
Function
b. DEVI
Monitoring of dynamic control valve behavior with the following parameters:
b1.TIM
Time constant
b2.LIMIT
Limit
Overview parameter C
Parameter
Function
C. LEAK
Monitoring of pneumatic leakage with the following parameters:
C1.LIMIT
Limit
152
Parameter values
0.0 ... 100.0
0.1 ... 2.0 ... 10.0
0.1 ... 10.0 ... 100.0
uP / do / uP do
OFF / On
0.1 ... 1.0 ... 100.0
NOINI / (C)##.# / FdInI / rEAL
0.1 ... 1.5 ... 100.0
0.1 ... 3.0 ... 100.0
0.1 ... 5.0 ... 100.0
Parameter values
Auto / 1 ... 400
0.1 ... 1.0 ... 100.0
0.1 ... 5.0 ... 100.0
0.1 ... 10.0 ... 100.0
0.1 ... 15.0 ... 100.0
Parameter values
0.1 ... 30.0 ... 100.0
0.1 ... 1.0 ... 100.0
0.1 ... 1.5 ... 100.0
0.1 ... 2.0 ... 100.0
Operating Instructions, 02/2016, A5E00074631-AB
Unit
%
%
%
Days
s
Unit
s
%
Unit
%
SIPART PS2 with and without HART