Commissioning
7.7 Device replacement
7. Mount the new, initialized positioner on the fixed actuator.
8. If the displayed actual position value differs from the noted value, correct the deviation by
moving the friction clutch.
9. Use the buttons on the positioner to enter the parameters which deviate from the factory
setting, such as type of actuator or tight closing.
10.Change to the measured value view using the
operating modes (Page 108)".
11.Release the fixing of the actuator.
See also
Sequence of automatic initialization (Page 117)
Automatic initialization of linear actuators (Page 125)
Automatic initialization of part-turn actuators (Page 132)
Manual initialization of linear actuators (Page 127)
Manual initialization of part-turn actuators (Page 134)