Siemens SIPART PS2 Operating Instructions Manual page 43

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

10.Select the row of holes. The selection of the row of holes depends on the yoke width of
11.Keep the positioner and the fastening bracket on the actuator. Ensure that the carrier pin
12.Tighten the pick-up bracket
13.Fasten the positioner on the yoke. Use the installation parts suitable for the
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
Figure 4-5
Installation with mounting bracket, flameproof enclosure
the actuator. Select the row of holes in such a way that the carrier pin
pick-up bracket
near the spindle. Ensure that the pick-up bracket
the clamping pieces
is guided inside the pick-up bracket
corresponding actuator.
Note
Height adjustment of the positioner
When you fasten the positioner on the yoke, the following applies to its height adjustment:
1. Set the height of the positioner in such a way that the horizontal lever position is near
the center of the stroke.
2. Orient yourself by the lever scale of the actuator.
3. If symmetrical mounting is not possible, you must always ensure that the horizontal
lever position is maintained within the range of stroke.
.
.
.
Installing/mounting
4.2 Mounting the linear actuator
meshes with the
does not touch