Diagnosis; Diagnostic Display - Siemens 6DR55 Series Manual

Electropneumatic positioner for linear and part--turn actuators
Table of Contents

Advertisement

4.5

Diagnosis

4.5.1 Diagnostic display

No.
Abbrevia--
Meaning
tion
1
STRKS
Number of strokes (Strokes)
2
CHDIR
Changes of direction (Changes of Direction)
3
Fault counter (Counter )
CNT
4
A1CNT
Alarm counter 1 (Alarm 1 Counter)
5
A2CNT
Alarm counter 2 (Alarm 2 Counter)
6
HOURS
Operating hours (Hours)
7
WAY
Determined actuating path (Way)
8
TUP
Travel time up (Travel Time Up)
9
TDOWN
Travel time down (Travel Time Down)
10
LEAK
Leakage (Leakage)
11
P0
Potentiometer value below stop (0%)
12
P100
Potentiometer value bottom stop (100%)
13
IMPUP
Impulse length up (Impulse Length Up)
14
IMPDN
Impulse length down (Impulse Length Down)
15
DBUP
Dead zone up (Dead Band Up)
16
DBDN
Dead zone down (Dead Band Down)
17
SSUP
Slow step zone up (Slow Step Zone Up)
18
SSDN
Slow step zone down (Slow Step Zone Down)
19
TEMP
Current temperature
20
TMIN
Minimum temperature ("drag pointer")
21
TMAX
Maximum temperature ("drag pointer")
22
T1
Number of operating hours in Temperature range 1
23
T2
Number of operating hours in Temperature range 2
24
T3
Number of operating hours in Temperature range 3
25
T4
Number of operating hours in Temperature range 4
26
T5
Number of operating hours in Temperature range 5
27
T6
Number of operating hours in Temperature range 6
SIPART PS2 PA Manual
A5E00127926--05
You go to the diagnostic display from automatic or manual operation by
simultaneously pressing all three keys for at least two seconds.
The following table shows an overview of the displayable values. In the
third column the corresponding English term from which the
abbreviation is derived is shown next to the German meaning unless
this is self explanatory.
The diagnostic display has a similar structure to in the "Configuration"
operating mode. the top line shows the value of the diagnostic variable,
the bottom line the number and abbreviation of the displayed variable.
The respective next diagnostic value can be selected with the operation
mode key
. By pressing and holding the operation mode key and
additionally pressing the decrement key
diagnostic values in reverse order.
Certain values can be set to zero by pressing the increment key
at least 5 seconds. This is noted in the last column in the table.
Some diagnostic values may be greater than 99999. In this case the
display switches to exponential display. Example: the value 1234567 is
displayed as 1.23E6.
you can select the
Displayable
Unit
values
0 to 4.29E9
--
0 to 4.29E9
--
0 to 4.29E9
--
0 to 4.29E9
--
0 to 4.29E9
--
0 to 4.29E9
Hours
0 to 130
mm or _
0 to 1000
s
0 to 1000
s
0.0 to 100.0
%
0.0 to 100.0
%
0.0 to 100.0
%
2 to 100
ms
2 to 100
ms
0.1 to 100.0
%
0.1 to 100.0
%
0.1 to 100.0
%
0.1 to 100.0
%
--40 to 85
_C
--40 to 85
_C
--40 to 85
_C
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
Operation
for
Rest
poss.
x
x
x
x
x
113

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sipart ps2 pa

Table of Contents