Automatic Initialization Of Linear Actuators - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

7.5.2

Automatic initialization of linear actuators

Requirements
The following conditions must be fulfilled before activating the automatic initialization:
1. The actuator spindle can be moved completely.
2. The actuator spindle is at a central position after moving.
Initializing the linear actuator automatically
Note
Interrupting initialization
An ongoing initialization can be interrupted at any time. To do this, press
configured until then are retained.
All parameters are reset to factory settings only if you have explicitly activated the preset
settings in the "PRST" parameter.
1. Switch to the "Configuration" mode. To do this, press the
2. Call the "2.YAGL" parameter. To do this, briefly press the
3. Check whether the value displayed in the "2.YAGL" parameter matches the setting of the
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
seconds. The display shows the following:
shown on the display depending on the setting:
transmission ratio selector. If required, change the setting of the transmission ratio
selector to 33° or 90°.
Commissioning
7.5 Commissioning linear actuators
. The settings
button for at least 5
button. The following is
125

Advertisement

Table of Contents
loading