Diagnostics; Diagnostic Display - Siemens SIPART PS2 6DR50xx Manual

Electropneumatic positioner for linear and part-turn actuators
Table of Contents

Advertisement

Operation
4.5
Diagnosis

4.5.1 Diagnostic display

No. Abbre-
Meaning
viation
1
STRKS
Number of strokes (Strokes)
2
CHDIR
Changes of direction (Changes of Direction)
3
Number of fault messages ( Counter)
CNT
4
A1CNT
Number of alarms 1 (Alarm 1 Counter)
5
A2CNT
Number of alarms 2 (Alarm 2 Counter)
6
HOURS
Operating hours (Hours)
7
WAY
Determined actuator travel (Way)
8
TUP
Actuating time up (Travel Time Up)
9
TDOWN
Actuating time down (Travel Time Down)
10
LEAK
Leakage (Leakage)
11
PST
Monitoring of the Partial Stroke Test
12
PRPST
Time since the last Partial Stroke Test
13
NXPST
Time until the next Partial Stroke Test
14
DEVI
General control valve malfunction
15
ONLK
Pneumatic leakage
16
STIC
Slipstick effect
17
ZERO
Zero point offset
18
OPEN
Shifting the upper stop
19
PAVG
Average position value
20
P0
Potentiometer value lower stop (0%)
122
To access the diagnostic display in automatic or manual mode,
press all three buttons for at least two seconds.
This following table gives an overview of the values that can be
displayed. The third column contains the term from which the
abbreviation is derived, unless it is self-explaining.
The structure of the diagnostic display is similar to that in "Configu-
ration" mode: the upper line shows the diagnosis value, the lower line
shows the number and abbreviation of the displayed value.
Use the operating mode button
By pressing and holding the operating mode button and simultaneously
pressing the decrement button
selected in reverse order.
Certain values can be set to zero by pressing the increment button
for at least 5 seconds. This is noted in the last table column.
Some diagnosis values can be greater than 99999. In this case, the
display switches to exponential indication. Example: the value for
1234567 is displayed as 1.23E6.
to select the next diagnosis value.
the diagnosis values can be
Values than
Unit
can be
indicated
0 to 4.29E9
--
0 to 4.29E9
--
0 to 4.29E9
--
0 to 4.29E9
--
0 to 4.29E9
--
0 to 4.29E9
hours
0 to 130
mm or _
0 to 1000
s
0 to 1000
s
P 0.0 to 100.0
%
OFF / ###.#,
s for ###.#
fdini, notSt,
SdtSt, fdtSt,
notd, Strt
###, notSt,
days
Sdtst, fdtSt
###, notSt,
days
SdtSt, fdtSt
Off, 0.0 to
%
100.0
Off, 0.0 to
--
100.0
Off, --100.0 to
%
100.0
Off, --100.0 to
%
100.0
Off, --100.0 to
%
100.0
0.0 to 100.0
%
0.0 to 100.0
%
SIPART PS2 Manual
A5E00074631--06