Alarm, error, and system messages
10.1 Output of system messages in the display
10.1.2

System messages during initialization

Remarks about the tables:
nn
/
Messages during initialization
Message
Line
Up
Down
P---
X
RUN1
X
RUN2
X
RUN3
X
RUN4
X
RUN5
X
YEND1
X
YEND2
X
RANGE
X
202
Stands for variable numeric values
Error symbol
(slash): the texts on the left and right of the slash flash alternately
Meaning/cause
Measuring range was exceeded, the potenti-
ometer is in the inactive zone, the transmis-
sion ratio selectors or the effective lever arm
are not adjusted as per the actuator travel
Initialization was started, part 1 is active (the
direction of action is determined)
Initialization part 2 is active (actuator travel
check and determination of endstops)
Initialization part 3 is active (determination
and display of travel times)
Initialization part 4 is active (determination of
the minimum controller increment length)
Initialization part 5 is active (optimization of
the transient response)
The first end position can be approached
only in case of a manual initialization
The second end position can be approached
only in case of a manual initialization
The end position or the measuring span is
beyond the permissible measuring range
only in case of a manual initialization
Measure
Switch the transmission ratio selector to
90°, especially in the case of part-turn ac-
tuators.
Adjust the effective lever length of linear
actuators as per the measuring range.
Wait.
Wait.
Wait.
Wait.
Wait until "FINSH" is displayed. Initializa-
tion was completed successfully.
1. Approach first end position using
key.
2. Acknowledge using
1. Approach second end position using
or
key.
2. Acknowledge using
Approach a different end position using
or
key and acknowledge using
key.
Move the friction clutch until "ok" is dis-
played, and then acknowledge with the
key.
Terminate the initialization process using
the
key, switch to the P-manual
mode, and correct the actuator travel and
the position displacement sensor.
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
or
key.
key.