Commissioning
7.5 Commissioning linear actuators
4. Set the "3.YWAY" parameter to determine the total stroke in mm. The setting of
parameter 3 is optional. The display shows the determined total stroke only at the end of
the initialization phase.
– Briefly press the
– Call the "3.YWAY" parameter. To do this, briefly press the
5. Call the "4.INITA" parameter. To do this, briefly press the
the following:
6. Start the initialization process. To do this, press the
the display shows the following:
The positioner runs through five initialization steps during the automatic initialization
process. Displays for the initialization steps from "RUN 1" to "RUN 5" are shown in the
lower line on the display. The initialization process depends on the actuator used, and
takes up to 15 minutes.
7. The following display indicates that the automatic initialization is complete:
126
button if you do not require any information about the total stroke
in mm. You are then directed to parameter 4.
shows the following:
Note
Set the "3.YWAY" parameter
Proceed as follows to set parameter 3:
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter with the buttons or to the read value.
button. The display
button. The display shows
button for at least 5 seconds until
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB