Tabular Overview Of The Parameters; Overview Of Initialization Parameters 1 To 5 - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

9.3

Tabular overview of the parameters

9.3.1

Overview of initialization parameters 1 to 5

Introduction
Parameters 1 to 5 are the same for all versions of the positioner. These parameters are used
to adjust the positioner to the actuator. Normally, setting these parameters is sufficient to be
able to operate the positioner on an actuator.
If you want to get to know all details of the positioner, gradually try out the effects of the
remaining parameters by systematic testing.
Note
Factory-set parameter values are printed in bold in the following table.
Overview
Parameter
Function
1.YFCT
Type of actuator
Linear actuator - carrier pin on actuator spindle
Linear actuator - external linear potentiometer
2.YAGL
Rated angle of rotation of positioner shaft
3.YWAY
Range of stroke (optional setting)
2)
4.INITA
Initialization (automatic)
5.INITM
Initialization (manual)
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
Part-turn actuator
Linear actuator
Part-turn actuator with NCS
Linear actuator with NCS
Linear actuator with NCS and lever
3)
9.3 Tabular overview of the parameters
Parameter values
Normal
turn
WAY
FWAY
LWAY
ncSt
ncSL
ncSLL
1)
5 | 10 | 15 | 20
(Short lever 33°, range of stroke 5 to 20
(Short lever 90°, range of stroke 25 to 35
40 | 50 | 60 | 70 | 90 | 110 | 130
(Long lever 90°, range of stroke 40 to 130
NOINI | no / ###.# | Strt
NOINI | no / ###.# | Strt
Parameter assignment
Inverted
-turn
-WAY
-FWAY
-LWAY
-ncSt
-ncSL
-ncLL
33°
90°
OFF
mm)
25 | 30 | 35
mm)
mm)
Unit
Degrees
mm
147