Device Replacement - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Commissioning

7.7 Device replacement

11.Press the
12.The initialization process is automatically resumed. Initialization steps "RUN1" to "RUN5"
are output in the bottom line of the display. The following display indicates that the
initialization has been completed successfully:
Aborting the manual initialization process
1. Press the
"Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the
3. The software status is displayed.
4. After releasing the
means that the positioner has not been initialized.
7.7
Device replacement
Introduction
Note
Initialization
The positioner can be replaced without having to interrupt ongoing processes. However,
copying and pasting of the initialization parameters only allows an approximate adjustment of
the positioner to your actuator. Following initialization, the positioner initially works with the
manually defined parameters.
• For this reason, an automatic or manual initialization should be carried out as soon as
possible.
Note
Deferred initialization
Initialize the new positioner as soon as possible. The following properties can be ensured
only after initializing:
• Optimum adjustment of the positioner as per the mechanical and dynamic properties of
the actuator.
• Non-deviating position of end stops
• Correctness of the maintenance data
136
button. The current position of the actuator is applied.
button. The display shows the "INITM" parameter. The positioner is in the
button, the positioner is in "P manual mode". "P manual mode"
button for at least 5 seconds.
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB