Inita' Initialization (Automatically); Initm' Initialization (Manual) - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with and without hart
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Parameter assignment
9.4 Description of parameters
9.4.1.4

'4.INITA' Initialization (automatically)

Possible settings:
Purpose:
Factory setting:
9.4.1.5

'5.INITM' Initialization (manual)

Possible settings:
Purpose:
Description:
Factory setting:
158
• NOINI
• no / ###.#
• Strt
Use this parameter to start the automatic initialization process.
1. Select the "Strt" setting.
2. Then press the
The sequence of the initialization process from "RUN1" to "RUN5"
is output in the bottom line of the display.
NOINI
• NOINI
• no / ###.#
• Strt
Use this parameter to start the manual initialization process.
1. Select the "Strt" setting.
2. Then press the
If the positioner has already been initialized and if the "4.INITA"
and "5.INITM" values are set, it is possible to reset the positioner
to the non-initialized status. To do this, press the
least 5 seconds.
NOINI
button for at least 5 seconds.
button for at least 5 seconds.
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
button for at