Technical data
12.8 Option modules
Electrically isolated from the basic
•
device
Signal status 0
Signal status 1
Internal resistance
Static destruction limit
•
Connecting to circuits with the
•
following peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
12.8.2
Position feedback module
Position feedback module
Direct current output for position
feedback
1 current output, terminals 61 and 62
Rated signal range
Dynamic range
Auxiliary voltage U
H
External load R
[kΩ]
B
Transmission error
Temperature influence
Resolution
Residual ripple
254
Without explosion protec-
tion or suitable for use in
the SIPART PS2 Ex d
± 35 V
-
-
-
The three outputs, the BI2 input and the basic device are galvanically isolated from
Without explosion protec-
tion or suitable for use in
the SIPART PS2 Ex d
6DR4004-8J
+12 ... +35 V
With Ex protection Ex "ia"
≤ 4.5 V or open
≥ 13 V
≥ 25 kΩ
-
U
= DC 25.2 V
i
C
= negligibly small
i
L
= negligibly small
i
each other.
DC 840 V, 1 s
With Ex protection Ex ia
(only in temperature class
T4)
6DR4004-6J
2-wire connection
4 ... 20 mA, short-circuit proof
3.6 ... 20.5 mA
+12 ... +30 V
≤ (U
[V] - 12 V)/I [mA]
H
≤ 0.3 %
≤ 0.1%/10 K (≤ 0.1%/18 °F)
≤ 0.1 %
≤ 1 %
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
With Ex protection
Ex "ic", "nA", "t"
-
"ic":
U
= DC 25.2 V
i
"nA"/"t":
U
≤ DC 25.5 V
n
C
= negligibly small
i
L
= negligibly small
i
With Ex protection
Ex "ic", "nA", "t"
6DR4004-6J
+12 ... +30 V