Technical data
12.8 Option modules
Electrically isolated from the basic
device
Signal status 0
Signal status 1
Internal resistance
Static destruction limit
Connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
12.8.2

Position feedback module

Position feedback module
Direct current output for position
feedback
1 current output, terminals 61 and 62
Rated signal range
Dynamic range
Auxiliary voltage U
H
External load R
[kΩ]
B
Transmission error
Temperature influence
Resolution
Residual ripple
254
Without explosion protec-
tion or suitable for use in
the SIPART PS2 Ex d
± 35 V
-
-
-
The three outputs, the BI2 input and the basic device are galvanically isolated from
Without explosion protec-
tion or suitable for use in
the SIPART PS2 Ex d
6DR4004-8J
+12 ... +35 V
With Ex protection Ex "ia"
≤ 4.5 V or open
≥ 13 V
≥ 25 kΩ
-
U
= DC 25.2 V
i
C
= negligibly small
i
L
= negligibly small
i
each other.
DC 840 V, 1 s
With Ex protection Ex ia
(only in temperature class
T4)
6DR4004-6J
2-wire connection
4 ... 20 mA, short-circuit proof
3.6 ... 20.5 mA
+12 ... +30 V
≤ (U
[V] - 12 V)/I [mA]
H
≤ 0.3 %
≤ 0.1%/10 K (≤ 0.1%/18 °F)
≤ 0.1 %
≤ 1 %
SIPART PS2 with and without HART
Operating Instructions, 02/2016, A5E00074631-AB
With Ex protection
Ex "ic", "nA", "t"
-
"ic":
U
= DC 25.2 V
i
"nA"/"t":
U
≤ DC 25.5 V
n
C
= negligibly small
i
L
= negligibly small
i
With Ex protection
Ex "ic", "nA", "t"
6DR4004-6J
+12 ... +30 V