Programming To Set Up Central Station Reporting; Basic Telephone Set Up In Rps; Basic Internet Protocol (Ip) - Bosch D9412GV4 Quick Reference Manual

V2.03
Hide thumbs Also See for D9412GV4:
Table of Contents

Advertisement

14
en | Programming to Set Up Central Station Reporting
5

Programming to Set Up Central Station Reporting

Notice!
In order to use the D9412GV4/D7412GV4 v2.00 Modem4 reporting format, the Central
Station receiver must be updated with the latest software for proper functionality and
operation.
Notice!
You can program these items using RPS (version 5.15 or greater) and the steps listed below.
You can also use keypad programming (refer to the D9412GV4/D7412GV4 v2.00 Program Entry
Guide).
5.1

Basic Telephone Set Up in RPS

1.
2.
3.
4.
5.
6.
5.2

Basic Internet Protocol (IP)

1.
2.
3.
4.
5.
Notice!
Enhanced Communications settings usually follow the recommendations of Central Stations'
staff. If using a B426, B420, ITS-DX4020, or ITS-DX4020-G for communication, refer to the
appropriate Installation and Operation Guide for more information.
Parameter
Enable Enhanced Communication
Path 1 Network Address
Path 1 Port Number
Path 1 Poll Rate (seconds)
Path 1 ACK Wait Time
Path 1 Retry Count
If the control panel is programmed to send a heartbeat poll to the Central Station, a rate of
1
75 sec maintains the virtual link in most network configurations.
2014.05 | 05 | F.01U.265.463
Go to PANEL WIDE PARAMETERS→ Phone and Phone Parameters.
Enter the primary telephone number in the Phone 1 field.
If a secondary telephone number is required, enter it in the Phone 2 field.
Go to Panel Wide Parameters→Communicator→Route Group 1.
Enter Phone 1 in the Primary Device field.
If a secondary telephone is required, enter Phone 2 in the Backup Device field.
Go to PANEL WIDE PARAMETERS→Communicator→Route Group 1 Primary Device.
Select SDI Address 88 Path 1.
Go to PANEL WIDE PARAMETERS→SDI RPS/Enhanced Comm→Enable Enhanced
Communications to Yes.
Go to PANEL WIDE PARAMETER→Enhanced Communications.
Select or enter the following values:
1
Quick Reference Guide
Value
YES
IP or Network address of Central Station
receiver
Port Number of Central Station receiver
Poll rate recommended by Central Station
13 sec (default setting)
5 (default setting)
Control Panel
Bosch Security Systems, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv4