4.213 Floor curing
• The floor curing function ensures controlled drying of the floor
The floor curing function maintains the flow temperature at a predefined temperature
profile with the help of the mixing valve.
Setting range
0...3
Selection of a temperature profile activates the floor curing function and the heating cir-
cuit ensures the preset flow temperatures.
0
Inactive
1
Functional heating
2
Floor curing heating
3
Functional and floor curing heating
4.213.1

Temperature profile

The following graph shows the temperature profile of the selected floor curing function.
[TVw]
TVmax
50
45
40
35
30
25
20
0
1
5
X
Fh
1
TVw
Flow temperature setpoint
x
Start day
Fh
Functional heating
Bh
Floor curing heating
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
Unit
7
1
5
Bh
Fh + Bh
Factory setting
0
10
15
18
25
[Tag
]
231/348