Mechanical installation
3.3 Installation
3.3.2.2
Requirements on the levelness of the floor
The foundation at the installation location of the cabinet devices must be level to ensure
proper functioning of the cabinet units.
● Care must be taken to ensure that the doors can be opened and closed and that the
● Flat sections (such as doors, side panels and hoods) must be sealed correctly to ensure
● When connecting cabinet units side-by-side, ensure that no air can enter through gaps.
Figure 3-2
The following points must be observed to ensure full functionality of the cabinet units:
● The foundation must be level.
● Irregularities must be leveled out.
● Gaps where air can enter caused by leveling measures (e.g.:
46
locking systems work properly.
compliance with the specified degree of protection.
Requirements on the levelness of the floor
sealed.
①
in the diagram) must be
Cabinet Modules
Manual, (GH5), 05/2010, A5E03263538A