Floor curing function

Floor curing function
Siemens Switzerland Ltd
HVAC Products
Line no.
HC1
HC2
HCP
850
1150
1450
851
1151
1451
1455
1456
1457
The floor curing function ensures controlled drying of the floor. It controls the flow
temperature according to a certain temperature profile. Drying of the floor is ensured by
the floor heating system and the mixing or pump heating circuit.
Off:
Function is deactivated.
Functional heating (Fh) :
The first part of the temperature profile is handled automatically.
Floor curing heating (Bh)
The second part of the temperature profile is handled automatically.
Floor curing heating and functional heating
The entire temperature profile (first and second part) is handled automatically.
Manually
It is not a temperature profile that is handled, but the floor setpoint is controlled
manually. The function is automatically ended after 25 days.
• Observe the relevant standards and regulations of the company making and laying
the floor!
• Proper functioning is ensured only when the plant is correctly installed (hydraulic
system, electrical installation, settings)!
If not observed, the floor might get damaged!
• The function can be aborted by selecting Off
• Maximum limitation of the flow temperature remains active
[TVw]
55
50
45
40
35
30
25
20
0
1
5
7
1
X
Fh
1
X
Start day
Fh
Functional heating
Bh
Floor curing heating
User manual RVS61.843
6 The settings in detail
Operating line
Floor curing function
Off
Functional heating (Fh)
Curing heating (Bh)
Functional/curing heating
Curing heating/functional heating
Manually
Floor curing setp manually
Floor curing setp current
Floor curing day current
Floor curing days completed
5
10
Bh
Fh + Bh
15
18
[Tag
]
25
CE1U2355en_02
23. November 2007
85/221