3.11 Switching times of time switch program 1

This is the setting of the switching times of time switch program at which the
temperature setpoints for the relevant heating circuit will change.
The heating program thus set becomes active with automatic mode
Setting range
- -:- -...24:00
First, select the weekday for which the switching times shall be entered!
The controller makes a final check to ensure the entries have been made in the correct
order.
At the times entered, the program will switch to the respective temperature setpoints.
The table below shows at what times the setpoints will be activated.
Entry:
– – : – –
Switching point inactive.
00:00...24:00At the time entered, heating to the respective temperature is ensured.
Line
Switching point
Switch-on time period 1
Switch-off time period 1
Switch-on time period 2
Switch-off time period 2
Switch-on time period 3
Switch-off time period 3
In AUTO mode, the time switch program can be set on both the controller (as described
above) and on the QAA70 room unit. It is always the last action that is active.
Basic Documentation RVA63.242, RVA53.242
Description of end-user settings
Unit
h : min
Temperature setpoint
Setpoint of knob
Reduced setpoint
Setpoint of knob
Reduced setpoint
Setpoint of knob
Reduced setpoint
.
Factory setting
See "Program overview"
below
Standard
06:00
22:00
– – : – –
– – : – –
– – : – –
– – : – –