Time Programs; Switching Points; Standard Program; Holidays - Siemens Albatros2 User Manual

Heat pump controller
Hide thumbs Also See for Albatros2:
Table of Contents

Advertisement

Entering the switching
times

Switching points

Standard program

Siemens Switzerland Ltd
HVAC Products
6.4

Time programs

For the heating circuits and DHW heating, a number of switching programs are
available. They are activated in Automatic mode and control the change of the
temperature levels (and the associated setpoints) via the selected switching times.
The switching times can be set in a combined way, either commonly for several days,
or separately for individual days. The preselection of groups of days like for instance
Mo...Fr and Sa...Su that use the same switching times simplifies setting of the switching
programs.
Line no.
HC1
HC2
3/HCP 4/DHW 5
500
520
540
560
501
521
541
561
502
522
542
562
503
523
543
563
504
524
544
564
505
525
545
565
506
526
546
566
Line no.
516, 536, 556, 576,
616
All time programs can be reset to their default settings. Each time program has its own
operating line to make the reset.
In that case, individual settings will be lost!
6.5

Holidays

Line no.
HC1
HC2
HC3P
642
652
662
643
653
663
648
658
668
The holiday program is used to switch the heating circuits to a selectable operating
level according to calendar dates.
Important
• The holiday program can only be used in "Automatic" mode
User manual RVS61.843
6 The settings in detail
Operating line
600
Preselection
Mo - Su
Mo - Fr
Sa - Su
Mo - Su
601
1. 1st phase on
602
1. 1st phase off
603
2. 2nd phase on
604
2. 2nd phase off
605
3. 3rd phase on
606
3. 3rd phase off
Operating line
Default values
No
Yes
Operating line
Start
End
Operating level
Frost protection
Reduced
75/221
CE1U2355en_02
23. November 2007